Single Core 90°C Thermosetting Insulated Cables, Unarmoured, With or Without Sheath (COPPER CONDUCTORS)

Tables Apply to: 6491B, 6181XY

CURRENT-CARRYING CAPACITY (amperes)

Conductor Cross Sectional AreaReference Method A (enclosed in conduit in thermally insulating wall etc.)Reference Method B (enclosed in conduit on a wall or in trunking etc.)Reference Method C (clipped direct)Reference Method F (in free air or on a perforated cable tray etc horizontal or vertical etc.)Reference Method G (in free air)
2 cables, single-phase a.c. or d.c.3 or 4 cables, three-phase a.c. 2 cables, single-phase a.c. or d.c.3 or 4 cables, three-phase a.c. 2 cables, single-phase a.c. or d.c. flat and touching3 or 4 cables, three-phase a.c. flat and touching or trefoil2 cables, single-phase a.c. or d.c. flat3 cables, three-phase a.c. flat3 cables, three-phase a.c. trefoil2 cables, single-phase a.c. or d.c. or 3 cables three-phase a.c. flat
HorizontalVertical
123456789101112
(mm2)(A)(A)(A)(A)(A)(A)(A)(A)(A)(A)(A)
1141317151917.5-----
1.5191723202523-----
2.5262331283431-----
4353142374641-----
6454054485954-----
10615475668174-----
1681731008810999-----
2510695133117143130161141135182161
35131117164144176161200176169226201
50158141198175228209242216207275246
70200179253222293268310279268353318
95241216306269355326377342328430389
120278249354312413379437400383500454
1503182853933424764036504464444577527
185362324449384545500575533510661605
240424380528450644590679634607781719
300486435603514743681783736703902833
400--6835848687939408688231,0851,008
500--7836669909041,0839989461,2531,169
630--9007641,1301,0331,2541,1511,0881,4541,362
800----1,2881,1791,3581,2751,2141,5811,485
1,000----1,4431,3231,5201,4361,3491,7751,671

NOTES :

  • Where a conductor operates at a temperature exceeding 70°C it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature (see Regulation 512.1.2)
  • Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70°C, the current ratings given in the equivalent table for 70°C thermoplastic insulated cables (Table 4D1A) must be used (see also Regulation 523.1)

VOLTAGE DROP (per ampere per metre)

Conductor Cross Sectional Area2 cables d.c2 cables, single-phase a.c.3 or 4 cables, three-phase a.c.
Reference Methods A&B (enclosed in trunking)Reference Methods C&F (clipped direct, on tray, or in free air)Reference Methods A&B (enclosed in conduit or trunking)Reference Methods C,F & G (clipped direct, on tray or in free air)
Cables touchingCables spaced*Cables touching, trefoilCables touching, flatCables spaced*, flat
123456789
(mm2)(mV/A/m)(mV/A/m)(mV/A/m)(mV/A/m)(mV/A/m)(mV/A/m)(mV/A/m)(mV/A/m)
14646464640404040
1.53131313127272727
2.51919191916161616
41212121210101010
67.97.97.97.96.86.86.86.8
104.74.74.74.74444
162.92.92.92.92.52.52.52.5
  rxzrxzrxzrxzrxzrxzrxz
251.851.850.311.91.850.191.851.850.281.851.60.271.651.61.1651.61.60.191.61.60.271.65
351.351.350.291.351.350.181.351.350.271.351.150.251.151.150.1551.151.150.181.151.150.261.2
500.9910.291.050.990.1810.990.2710.870.250.90.860.1550.870.860.180.870.860.260.89
700.680.70.280.750.680.1750.710.680.260.730.60.240.650.590.150.610.590.1750.620.590.250.65
950.490.510.270.580.490.170.520.490.260.560.440.230.50.430.1450.450.430.170.460.430.250.49
1200.390.410.260.480.390.1650.430.390.250.470.350.230.420.340.140.370.340.1650.380.340.240.42
1500.320.330.260.430.320.1650.360.320.250.410.290.230.370.280.140.310.280.1650.320.280.240.37
1850.250.270.260.370.260.1650.30.250.250.360.230.230.320.220.140.260.220.1650.280.220.240.33
2400.190.210.260.330.20.160.250.1950.250.310.1850.220.290.170.140.220.170.1650.240.170.240.29
3000.1550.1750.250.310.160.160.220.1550.250.290.150.220.270.140.140.1950.1350.160.210.1350.240.27
4000.120.140.250.290.130.1550.20.1250.240.270.1250.220.250.110.1350.1750.110.160.1950.110.240.26
5000.0930.120.250.280.1050.1550.1850.0980.240.260.10.220.240.090.1350.160.0880.160.180.0850.240.25
6300.0720.10.250.270.0860.1550.1750.0780.240.250.0880.210.230.0740.1350.150.0710.160.170.0680.230.24
8000.056 - 0.0720.150.170.0640.240.25 - 0.0620.130.1450.0590.1550.1650.0550.230.24
1,0000.045 - 0.0630.150.1650.0540.240.24 - 0.0550.130.140.050.1550.1650.0470.230.24

NOTE: *Spacings larger than one cable diameter will result in a larger voltage drop.