Multicore 70°C Thermoplastic Insulated and Thermoplastic Sheathed Cables, Non Armoured (COPPER CONDUCTORS)

Tables Apply to: Firesure, Firesure 500, Firesure Plus, Multiuse,(Twin and Earth see also TABLE 4D5)

CURRENT-CARRYING CAPACITY (amperes)

Conductor Cross Sectional Area Reference Method A (enclosed in conduit in thermally insulating wall etc.) Reference Method B (enclosed in conduit on a wall or in trunking etc.) Reference Method C (clipped direct) Reference Method E (free air or on a perforated cable tray etc, horizontal or vertical)
1 two-core cable* single-phase a.c. or d.c. 1 three-core cable* or 1 four-core cable, three-phase a.c. 1 two-core cable* single-phase a.c. or d.c. 1 three-core cable* or 1 four-core cable, three-phase a.c. 1 two-core cable* single-phase a.c. or d.c. 1 three-core cable* or 1 four-core cable, three-phase a.c. 1 two-core cable* single-phase a.c. or d.c. 1 three-core cable* or 1 four-core cable, three-phase a.c.
1 2 3 4 5 6 7 8 9
(mm2)(A)(A)(A)(A)(A)(A)(A)(A)
111101311.51513.51714.5
1.5141316.51519.517.52218.5
2.518.517.5232027243025
42523302736324034
63229383446415143
104339524663577060
165752696285769480

* with or without a protective conductor.

VOLTAGE DROP (per ampere per metre)

Conductor Two-core cable d.c. Two-core cableThree- or four-core cable,
cross-sectional area single-phase a.c.three-phase a.c.
1234
(mm2)(mV/A/m)(mV/A/m)(mV/A/m)
1444438
1.5292925
2.5181815
411119.5
67.37.36.4
104.44.43.8
162.82.82.4

DISCLAIMER: This information has been supplied in good faith and the upmost care has been taken to ensure the data is accurate in it's derivation from BS7671.
However, this information should not be considered as a substitute for BS7671, which should always be referred to. It remains the responsibility of the user to ensure all data and assumptions are correct and that any cable used is suitable for its intended purpose.