Single Core 70°C Thermoplastic Insulated Cables, Non Armoured, With or Without Sheath (COPPER CONDUCTORS)

Tables Apply to: ST91X, 6491X, 6181Y, TRI-RATED (when installed in conduit or trunking)

CURRENT-CARRYING CAPACITY (amperes)

Conductor Cross Sectional AreaReference Method A (enclosed in conduit in thermally insulating wall etc.)Reference Method B (enclosed in conduit on a wall or in trunking etc.)Reference Method C (clipped direct)Reference Method F (in free air or on a perforated cable tray horizontal or vertical etc.)
TouchingSpaced by one diameter
2 cables, single-phase a.c. or d.c.3 or 4 cables, three-phase a.c. 2 cables, single-phase a.c. or d.c.3 or 4 cables, three-phase a.c. 2 cables, single-phase a.c. or d.c. flat and touching3 or 4 cables, three-phase a.c. flat and touching or trefoil2 cables, single-phase a.c. or d.c. flat3 cables, three-phase a.c. flat3 cables, three-phase a.c. trefoil2 cables, single-phase a.c. or d.c. or 3 cables three-phase a.c. flat
HorizontalVertical
123456789101112
(mm2)(A)(A)(A)(A)(A)(A)(A)(A)(A)(A)(A)
11110.513.51215.514-----
1.514.513.517.515.52018-----
            
2.5201824212725-----
4262432283733-----
6343141364743-----
10464257506559-----
16615976688779-----
            
25807310189114104131114110146130
359989125110141129162143137181162
50119108151134182167196174167219197
70151136192171234214251225216281254
95182164232207284261304275264341311
120210188269239330303352321308396362
150240216300262381349406372356456419
185273245341296436400463427409521480
240321286400346515472546507485615569
300367328458394594545629587561709659
            
400--546467694634754689656852795
500--626533792723868789749982920
630--7206119048261,0059058551,1381,070
800----1,0309431,0861,0209711,2651,188
1000----1,1541,0581,2161,1491,0791,4201,337

VOLTAGE DROP (per ampere per metre)

Conductor Cross Sectional Area2 cables d.c2 cables, single-phase a.c.3 or 4 cables, three-phase a.c.
Reference Methods A&B (enclosed in trunking)Reference Methods C&F (clipped direct, on tray, or in free air)Reference Methods A&B (enclosed in conduit or trunking)Reference Methods C&F (clipped direct, on tray or in free air)
Cables touchingCables spaced*Cables touching, trefoilCables touching, flatCables spaced*, flat
123456789
(mm2)(mV/A/m)(mV/A/m)(mV/A/m)(mV/A/m)(mV/A/m)(mV/A/m)(mV/A/m)(mV/A/m)
14444444438383838
1.52929292925252525
2.51818181815151515
4111111119.59.59.59.5
67.37.37.37.36.46.46.46.4
104.44.44.44.43.83.83.83.8
162.82.82.82.82.42.42.42.4
  rxzrxzrxzrxzrxzrxzrxz
251.751.80.331.81.750.21.751.750.291.81.50.291.551.50.1751.51.50.251.551.50.321.55
351.251.30.311.31.250.1951.251.250.281.31.10.271.11.10.171.11.10.241.11.10.321.15
500.930.950.310.930.190.950.930.280.970.810.260.850.80.1650.820.80.240.840.80.320.86
700.630.650.290.720.630.1850.660.630.270.690.560.250.610.550.160.570.550.240.60.550.310.51
950.460.490.280.560.470.180.50.470.270.540.420.240.480.410.1550.430.410.230.470.40.310.51
1200.360.390.270.470.370.1750.410.370.260.450.330.230.410.320.150.360.320.230.40.320.30.44
1500.290.310.270.410.30.1750.340.290.260.390.270.230.360.260.150.30.260.230.340.260.30.4
1850.230.250.270.370.240.170.290.240.260.350.220.230.320.210.1450.260.210.220.310.210.30.36
2400.180.1950.260.330.1950.1650.250.1850.250.310.170.230.290.160.1450.220.160.220.270.160.290.34
3000.1450.160.260.310.150.1650.220.150.250.290.140.230.270.130.140.190.130.220.250.130.290.32
4000.1050.130.260.290.120.160.20.1150.250.270.120.220.250.1050.140.1750.1050.210.240.10.290.31
5000.0860.110.260.270.0980.1550.1850.0930.240.260.10.220.250.0860.1350.160.0860.210.230.0810.290.3
6300.0680.0940.250.270.0810.1550.1750.0760.240.250.080.220.240.0720.1350.150.0720.210.220.0660.280.29
8000.053-  0.0680.150.1650.0610.240.25-  0.060.130.1450.060.210.220.0530.280.29
10000.042-  0.0590.150.160.050.240.24-  0.0520.130.140.0520.20.210.0440.280.28

NOTE: *Spacings larger than one cable diameter will result in a larger voltage drop.

DISCLAIMER: This information has been supplied in good faith and the upmost care has been taken to ensure the data is accurate in it's derivation from BS7671.
However, this information should not be considered as a substitute for BS7671, which should always be referred to. It remains the responsibility of the user to ensure all data and assumptions are correct and that any cable used is suitable for its intended purpose.