    Specification

    Conductor

    • Plain Annealed Copper Class 1 or 2 to BS EN 60228

    Insulation

    • Silicone Rubber Type EI2 to BS EN 50363-1

    Sheath

    • Thermoplastic LSNH Type LTS 3 to BS 7655-6.1

    Min Operating Temperature

    • -15°C

    Max Operating Temperature

    • 70°C

    Min Bending Radius

    • 6 x ∅

    Core Colours

    • 2 core - Blue and Brown (plus CPC)
    • 3 core - Brown, Black and Grey (plus CPC)
    • 4 core - Blue, Brown, Black and Grey (plus CPC)

    Sheath Colours

    • red or white (other colours on request)

    Current Carrying Capacity

    • For current ratings refer to table 4D2 of BS7671 IEE Wiring Regulations

    Firesure® 500 - Designed for easier stripability

    Product Code: FIRESURE 500

    Product Description

    Manufactured to BS 7629-1 Table 2

    Plain Annealed Copper Conductors / Silicone Rubber Insulated / Circuit Protective Conductor / Single Layer of Aluminium/Co-Polymer Tape (tape is adhered to the sheathing and will come away with the sheath when stripping the cable) Thermoplastic Low Smoke Non-Halogen (LSNH) Sheath. 300/500V

    These cables are suitable for both indoor and outdoor applications in suitably protected environments and is particularly appropriate for direct burial in plaster, clipped directly to surface, tray and other installations requiring a dressable product.


    Conductor: Plain Annealed Copper Class 1 or 2 to BS EN 60228.
    Insulation: Silicone Rubber Type EI2 to BS EN 50363-1.
    Screen: Single Aluminium/Co-Polymer Screen In Direct Contact With Tinned Annealed Copper CPC. PRoviding excellent Earthing Characteristics.
    Binding Tape: 'Easy tear' polyester tape which allows easier removal of the sheath.
    Sheath: Thermoplastic LSNH Type LTS 3 to BS 7655-6.1
    Current Ratings: For current ratings refer to table 4D2 of BS7671 IEE Wiring Regulations.

    Product Details

    Reference NumberNumber and Nominal Cross Sectional Area of Conductors (mm2)Nominal Stranding of Conductor (mm)Nominal Stranding of CPC (mm)Nominal Radial Thickness of insulation (mm)Nominal Radial Thickness of Sheath (mm)Nominal Overall Diameter (mm)Approximate Weight (kg/km)
    HFS5002C1.52 x 1.51/1.381/1.380.70.97.895
    HFS5002C2.52 x 2.51/1.781/1.780.81.08.9140
    HFS5002C4.02 x 4.07/0.857/0.850.81.110.9231
    HFS5003C1.53 x 1.51/1.381/1.380.70.98.3120
    HFS5003C2.53 x 2.51/1.781/1.780.81.010.1195
    HFS5004C1.54 x 1.51/1.381/1.380.71.09.2140

    Other sizes available.