H694-XL XLPE/LSNH/SWA/LSNH

H 6942X 2.5 STRANDED XLPE/LSNH/SWA/LSNH

These cables are designed to be used in installations where smoke and acid gas emission would pose a major hazard in the event of a fire. Steel Wire Armoured cables are predominantly used for industrial wiring and mains distribution. They are designed to be used in industrial areas, in and around buildings and other similar environments. These cables are designed to be installed in air, clipped to surface, on cable tray/ladder work, embedded in concrete and buried direct or in ducting underground
SKU: H6942XL2.5LSNH
Product Group: H694-XL LSNH
Supplier: Doncaster Cables

Quick Facts


SKU
H6942XL2.5LSNH
Product Group
H694-XL LSNH
Specifications
34

Technical Specifications

Weight
262.52
Unit
1000
Number of conductors
2
Conductor Size
2.5
Construction
Plain Annealed Copper Conductor / XLPE Insulated / LSNH Bedded / Galvanised Steel Wire Armour / LSNH Sheathed. 600/1000V
Standard
BS 6724
Table / Clause
Table 6 (2 Core) Table 8 (3 Core) Table 10 (4 Core) Table 13 (5 Core)
Conductor
Plain Annealed Copper Class 2 Stranded to BS EN 60228
Insulation
Thermosetting XLPE Type GP8 to BS 7655-1.3
Bedding
Compatible LSNH Polymeric Material (LSNH)
Armouring
Galvanised Steel Wire
Sheathing
LSNH Type LTS1 to BS 7655-6.1
Voltage Rating
600/1000V
Minimum Operating Temperature
-15°C
Maximum Operating Temperature
90°C
Minimum Bending Radius
8 x diameter
Colour
Black
Core Colours
Blue and Brown
Current Ratings
For current ratings refer to table 4E4A of BS7671 IET Wiring Regulations.
Current Rating (In Air (A))
Table 4E4A of BS7671 IET Wiring Regulations Reference Method E
Current Rating (In Ground (B))
Table 4E4A of BS7671 IET Wiring Regulations Reference Method D
Nominal Stranding of Conductor (mm)
7/0.67
Nominal Radial Thickness of Insulation (mm)
0.7
Nominal Radial Thickness of Sheath (mm)
1.4
Nominal Radial Thickness of Bedding (mm)
0.8
Approximate Overall Diameter (mm)
12.6
Approximate Weight (kg/km)
260
Recommended Gland Size
20S
Galv. Steel Wire Armour
0.9
Cable Types
LSNH MULTICORE STEEL WIRE ARMOUR
Conductor Class to BS EN 60228
Class 2
Nominal Diameter of Armour Wire (mm)
0.9
Bullet1
BASEC Approved
Bullet2
Tested and quality assured by Doncaster Cables

No specifications found matching ""