Conductor
Insulation
Min Operating Temperature
Max Operating Temperature
Min Bending Radius
Core Colours
Current Carrying Capacity
Manufactured to BS EN 50525-2-31:2011 Clause 4.1, Table B.1
Annealed Copper Conductor / PVC Insulated. 450/750V*
Suitable for fixed protected installation in or on light fittings and inside applications, switchgear and controlgear, for voltages up to 750V a.c or up to 450V to earth d.c.. When installed in an earthed metal enclosure, cables are suitable for voltages up to 1000V a.c or up to 750V to earth d.c.
Reference Number | Harmonisation Code | Nominal Cross Sectional Area of Conductor (mm2) | Nominal Stranding of Conductor (mm) | Nominal Radial Thickness of insulation (mm) | Overall Diameter Lower Limit (mm) | Overall Diameter Upper Limit (mm) | Approximate Weight kg/km) |
---|---|---|---|---|---|---|---|
6491X | HO5V-U | 1.0* | 1 / 1.13 | 0.6 | 2.2 | 2.7 | 15 |
6491X | HO7V-U | 1.5 | 1 / 1.38 | 0.7 | 2.6 | 3.2 | 21 |
ST91X | HO7V-R | 1.5 | 7 / 0.53 | 0.7 | 2.7 | 3.3 | 21 |
6491X | HO7V-U | 2.5 | 1 / 1.78 | 0.8 | 3.2 | 3.9 | 33 |
ST91X | HO7V-R | 2.5 | 7 / 0.67 | 0.8 | 3.3 | 4.0 | 35 |
6491X | HO7V-R | 4.0 | 7 / 0.85 | 0.8 | 3.8 | 4.6 | 50 |
6491X | HO7V-R | 6.0 | 7 / 1.04 | 0.8 | 4.3 | 5.2 | 70 |
6491X | HO7V-R | 10.0 | 7 / 1.35 | 1.0 | 5.6 | 6.7 | 120 |
6491X | HO7V-R | 16.0 | 7 / 1.70 | 1.0 | 6.4 | 7.8 | 175 |
6491X | HO7V-R | 25.0 | 7 / 2.14 | 1.2 | 8.1 | 9.7 | 290 |
6491X | HO7V-R | 35.0 | 7 / 2.52 | 1.2 | 9.0 | 10.9 | 400 |
6491X | HO7V-R | 50.0 | 19 / 1.78 | 1.4 | 10.6 | 12.8 | 565 |
6491X | HO7V-R | 70.0 | 19 / 2.14 | 1.4 | 12.1 | 14.6 | 770 |
6491X | HO7V-R | 95.0 | 19 / 2.52 | 1.6 | 14.1 | 17.1 | 1010 |
6491X | HO7V-R | 120.0 | 37 / 2.03 | 1.6 | 15.6 | 18.8 | 1260 |
6491X | HO7V-R | 150.0 | 37 / 2.25 | 1.8 | 17.3 | 20.9 | 1522 |
6491X | HO7V-R | 185.0 | 37 / 2.52 | 2.0 | 19.3 | 23.3 | 1900 |
6491X | HO7V-R | 240.0 | 61/2.25 | 2.2 | 22.0 | 26.6 | 2490 |
6491X | HO7V-R | 300.0** | 61/2.52 | 2.4 | 24.5 | 29.6 | 3100 |
Copyright Doncaster Cables 2024 All Rights Reserved | Company Policies